Regulation for the management of low-temperature radiant heating and cooling systems with anti-condensation expanded polystyrene insulation shell. The variable speed pump is a circulator with a permanent magnet synchronous motor, reaches efficiency values up to EEI ≤ 0.20 and is controlled by an inverter with a power supply voltage of 230 Vac at a frequency of 50 Hz and a min. consumption of 3 W and max. 225 W. The servomotor can receive a three-point control, has a stroke time (open/close) of 120 sec., a power supply of 230 Vac at a frequency of 50 Hz and a consumption of 8 W. The mixing valve has a rotating spherical element to optimise mixing accuracy. Suitable for installation in central heating plants and can be installed horizontally and vertically. Recommended in combination with the Eurotherm Smartcomfort climate control system. The regulation consists of: electronic retarder, flow probe well, variable speed pump, servomotor, 3-way mixing valve, full flow valve with thermometer for flow temperature, full flow valve with thermometer for return temperature, complete with full flow shut-off valves. Kv of the entire regulation = 8.5. The maximum indicative flow rates are 2000 l/h (R), 4000 l/h (TOP), 6000 l/h (SUPER).
1. return thermometer with ball valve
2. flow thermometer with ball valve
3. safety thermostat with retarder
4. thermowell for flow sensor
5. electronic circulator
6. anticondensation cover
7. three-way mixing valve
Nuova Compamat R
Flow rate 1850 l/h
Heating surface 185 m2
Hp. Δt =6° C , P= 70 W/m2
Circulator EEI ≤0.20
Nuova Compamat TOP
Flow rate 4000 l/h
Heating surface 400 m2
Hp. Δt =6° C , P= 70 W/m2
Circulator EEI ≤0.23
Nuova Compamat SUPER
Flow rate 6000 l/h
Heating surface 600 m2
Hp. Δt =6° C , P= 70 W/m2
Circulator EEI ≤0.23